Specifications / Models NOVOS 3 CO2+VOC NOVOS 3 CO2 NOVOS 3 VOC
Measured values CO2, VOC, temperature + humidity (depending on the device), each output can be set to get a variable mix of CO2 and VOC by configuration CO2, temperature + humidity (depending on the device) VOC, temperature + humidity (depending on the device)
Output voltage VV: 2x 0..10 V, 3xV: 3x 0..10 V, 4xV: 4x 0..10 V, 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ V: 1x 0..10 V, VV: 2x 0..10 V, 3xV: 3x 0..10 V, 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ V: 1x 0..10 V, VV: 2x 0..10 V, 3xV: 3x 0..10 V, 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ
Output current AA: 2x 4..20 mA, 3xA: 3x 4..20 mA, 4xA: 4x 4..20 mA, max. load 500 Ω A: 1x 4..20 mA, AA: 2x 4..20 mA, 3xA: 3x 4..20 mA, max. load 500 Ω A: 1x 4..20 mA, AA: 2x 4..20 mA, 3xA: 3x 4..20 mA, max. load 500 Ω
Network technology RS485 BACnet (MS/TP), RS485 Modbus BACnet MS/TP, RS485 Modbus RS485 BACnet (MS/TP), RS485 Modbus
Power supply 15..35 V = or 19..29 V ~ SELV, AA | 3xA | 4xA:, 15..35 V = SELV 15..35 V = or 19..29 V ~ SELV, A | AA | 3xA:, 15..35 V = SELV 15..35 V = or 19..29 V ~ SELV, A | AA | 3xA:, 15..35 V = SELV
Measuring range humidity 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS
Measuring range CO2 (for models CO2+VOC and CO2) 0..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS 0..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS N/A
Accuracy temperature ±0,5 K (typ. at 21 °C) ±0,5 K (typ. at 21 °C) ±0,5 K (typ. at 21 °C)
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C) ±2% between 10..90% rH (typ. at 21 °C) ±2% between 10..90% rH (typ. at 21 °C)
Accuracy CO2 (for models CO2+VOC and CO2) ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) N/A
Calibration self-calibration, CO2: Dual Channel self-calibration, Dual Channel self-calibration
Sensor VOC sensor (heated metal oxide semiconductor), CO2: NDIR (non-dispersive, infrared) NDIR (non-dispersive, infrared) VOC sensor (heated metal oxide semiconductor)
Inputs RS485 Modbus:, 1x input for floating contact RS485 Modbus:, 1x input for floating contact RS485 Modbus:, 1x input for floating contact
Display RGB-LED indicating air quality (traffic light function ‘TLF’), optional RGB-LED indicating air quality (traffic light function ‘TLF’), optional RGB-LED indicating air quality (traffic light function ‘TLF’), optional
Colour pure white, black or aluminium pure white, black or aluminium pure white, black or aluminium
Enclosure PC V0, optionally with design cover black or aluminium PC V0, optionally with design cover black or aluminium PC V0, optionally with design cover black or aluminium
Protection (IP) IP20 according to EN 60529 IP20 according to EN 60529 IP20 according to EN 60529
Cable entry rear entry, breaking points bottom, drill mark top rear entry, breaking points bottom, drill mark top rear entry, breaking points bottom, drill mark top
Electrical connection tool-free mountable spring clamp, max. 1,5 mm² tool-free mountable spring clamp, max. 1,5 mm² tool-free mountable spring clamp, max. 1,5 mm²
Ambient condition 0..+50 °C, max. 85% rH non-condensing 0..+50 °C, max. 85% rH non-condensing 0..+50 °C, max. 85% rH non-condensing
Mounting flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately
Notes for configuration an optional programming dongle (Bluetooth) is available (refer to accessories), mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) for configuration an optional programming dongle (Bluetooth) is available (refer to accessories) for configuration an optional programming dongle (Bluetooth) is available (refer to accessories), mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...)